Power's Flexible Series wide temperature battery UPS is an excellent
choice for those applications that require battery backup with good
surge protection, a wide temperature battery for usage in more extreme
environments, and the flexibility of being able to add additional
battery cabinets for extended run-time.
Typical
Applications
UPs-400Wtb is the ideal UPS for
computer or telecommunications equipment in extreme wide temperature
(-20o to +60oC) environments where ac power
delivery is unreliable and long battery backup times may be necessary.
The UPs-400Wtb is suitable
where power outages are a regular occurrence, or in areas where
utilities need to conduct rolling blackouts.
Key Benefits of
the UPs-400Wtb
The
UPs-400Wtb protects connected equipment from: power supply failure,
erroring, system lockups and re-boots. It contributes to enhanced
systems operation, greater reliability, improved repeatability, and
extended operating life.
Typical back-up time fully loaded is 8 minutes,
but 20 minutes can be obtained when the unit is loaded to 50% of its
capacity. Thus, an application requiring 200VA can be provided with 20
minutes of hold-up. The
capability of adding extra EXt-400Wtb external battery packs also makes
this a very cost-effective choice for enabling nearly unlimited holdup
times. Custom Settings: DIP switches in the rear panel
allow the user to set brownout sensitivity, inverter operating
frequency, or alarm mode, for complete flexibility and control of the
UPS.
How the
UPs-400Wtb
Works
The UPs-400WTB continually provides
surge protection with a capacitive element, and coordinated MOV surge
protection. Upon loss of power, the audible alarm beeps about once a
second, as the battery inverter kicks in within 8ms, which means
equipment will continue to operate without interruption.
When the battery level drops until only a
few minutes of holdup time remain, the alarm will beep, and the LED will
flash more rapidly, alerting of impending shutdown. A DB-9 female
connector provides communications capability with monitoring software
which can safely save open files and automatically shutdown your
systems.
|
| |
Specifications |
UPs-400Wtb |
| |
Electrical |
|
Capacity in VA (Watts) |
400
VA (250 W) |
| |
UPS type |
Single conversion
standby with 4-8 ms transfer time
|
| |
Input |
| |
Nominal voltage |
120
volts ac, single phase |
| |
Operating voltage |
95
- 135 volts AC. 47~63 Hz, sinusoidal. |
| |
AC input cord |
6
foot long cord with NEMA 5-15P plug. |
| |
Output |
| |
Nominal voltage |
120
volts ac, single phase. Inverter output: 105 - 130vacRMS |
| |
Nominal frequency |
50/60
Hz +/-3 Hz (user-selectable) |
| |
Power efficiency |
98% or higher during
ac
operation,
80% or higher during battery inverter operation. |
| |
Transfer time |
4-
8 ms typical between ac and inverter |
| |
Battery back-up time
(For
more time see below) |
8 minutes @ full load
(250 watts)
20 minutes @ half load (125 watts)
|
| |
Recharge time |
8
hours to return to 90% capacity after full discharge. |
| |
Optional # EXt-400
Extra
battery pack for
longer back-Up time
w/Anderson SB50 connector |
A
matching extra battery cabinet with separate charger, supplying
an additional 40 minutes @ full load, 90 minutes @ half load.
With a weight of 15.9kg (35 lbs), & same size as the UPs-400Wtb,
EXt-400’s battery recharge time is 12 hours to 90% capacity. |
| |
Surge protection |
MOV - transient surge suppression. |
| |
Surge test conditions |
ANSI/IEEE
C62.41-1991 test pulse,
Category A3, Ring Wave, 6000V, 200A. |
| |
Indicators and alarms |
LED
indicators & audible signals: ac, inverter, and battery status. |
| |
Communications interface |
DB-9
female connector provides communications capability
with optional monitoring or automatic shutdown feature.
|
| |
Ac output receptacles |
2
(NEMA 5-15R) |
| |
Physical |
| |
Dimensions |
125mm(5")wide x 178mm(7")high x
394mm(16")deep
|
| |
Weight |
9.1 kg (22 lbs) |
| |
Safety |
| |
Safety standards |
Designed to meet UL
& cUL 1778 standards
|
| |
Safety and reliability |
External fuse protects
all ac circuits.
Internal fuses protect all dc circuits.
Durable, all-steel chassis withstands transport in hostile
environments and operation in any indoor application.
|
| |
Environmental |
| |
Ambient temperature |
-20
to +60°C,
90% relative humidity (non-condensing at 25°C) |
| |
Warranty |
| |
Limited Warranty |
2
years, parts and labor. 1 year on batteries. |
|
TSi's ongoing product
improvement process makes specifications subject
to change. Other
companies product names herein are for identification purposes only, and
may be trademarks of their respective companies. |
UPs-400Wtb System
Architecture

TSi Power also manufactures
custom UPS. For special applications, please call.