The TSi Power Corporation Home Page White Papers On Power Protection Strategies and Technologies Press Releases and News on TSi Power Corporation TSi Power & Surge Protection Products Overview Line Conditioners, Automatic Voltage Regulators, Low-Impedance and Ferroresonant Isolation Transformers Ac Automatic Voltage Regulators, Precision PWM, Tap-Switching and Ferroresonant Topologies Unipolar PWM Sine Wave Output Dc to Ac Inverters Automatic Transfer Switches For Enabling Redundant Power Sources e.g. 2 UPS Indoor Uninterruptible Power Systems Outdoor UPS With Extreme Wide Temperature Batteries for Harsh Environments Accessories for TSi Products, such as Rack-mounting Kits, Extra Battery Cabinets, etc. Pricing, RFQ's, RFP's and Getting Formal Quotations Frequently Asked Questions URL Links to some of TSi Power's Favorite Websites URL Link to the Free Adobe Acrobat PDF Reader Download Page

 * Best Viewed In Internet Explorer

 

ILc Series 
230V, 15/30A 2400/3600VA

Ac low-impedance
isolation transformer
line conditioner

ILc-2400-3600 VA, 230VAC, 15A-30A, AC Low-Impedance Isolation Transformer Line Conditioner

 

Click here for complete specifications in 
a printer friendly Adobe Acrobat PDF format

TSi Power’s ILc Series Line Conditioner provides the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line ~ the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.

Typical ILc Line Conditioner Applications
Designed for situations where reliability and predictability matter to the enterprise. 
Examples include: point-of-sale terminals, telecommunications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key ILc Power Conditioning Benefits
ILc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. 
In addition, a reduction in equipment down time and service costs can be expected.

How ILc Line Conditioners Work
The integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC 61312.3.


Key Features of the TSi Power Isolation Line Conditioner
Coordinated surge protection
per IEC 61312.3
Low-impedance 
isolation transformer
True isolation
Common-mode noise elimination
High efficiency

 

Advanced noise and interference
filter reduces dV/dt from
6kV/µS to less than 10V/µS
on/off rocker style power switch
Quiet operation
Low weight
5 year warranty

 

   SPECIFICATIONS ILc-2400 ILc-3600
    Electrical

 

   Capacity in VA (Watts) 2400 VA (2400 watts) 3600 VA (3600 watts)
     Transformer Type Low-impedance E-I core isolation transformer
    Input
     Nominal voltage 208/220/230 or 240 volts ac, single phase
     Operating voltage 190 ~ 250 volts ac
     Nominal frequency  60 Hz +/-3
     Circuit breaker rating 15 amp 20 amps
     Ac input cord Hardwire (terminal block connector)
    Output
     Nominal voltage 208/220/230 or 240 volts ac, single phase
     Power efficiency 97% (typical)
     Total harmonic distortion < 1%
     Surge protection A three stage surge protection system consisting of 
isolation transformer, capacitor and M.O.V. is included.
     Surge test conditions Per ANSI/IEEE C62.41-1991 test waveforms
     Surge let-through voltages Single pulse: L-N: 50V, L-G: 50V, N-G: 0.5V
Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V
Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V
The measured rate of voltage rise/fall (dV/dt of the remnant waveform 
is less than 10V/
mS with input test waveform dV/dt of 6kV/mS.
     Power on/off On/off rocker style power switch/circuit breaker
     Indicators Green LED indicates ac power is present
     Ac receptacles
   (Other options available)
Hardwired output terminals (L1, neutral, and ground) are standard. Optional ac receptacles are available
    Physical
     Dimensions 254mm (10")wide x 190mm (7.5")high x 368mm (14.5")deep
     Weight 27.3 kg (60 lbs) 36.3 kg (80 lbs)
    Safety
     Agency approvals Designed to meet UL/cUL and IEC standards
     Overcurrent protection User resettable circuit breaker built-in
    Environmental
     Ambient temperature 0 to +40°C, 90% Relative Humidity (non-condensing)
    Warranty
     Warranty 5 year limited warranty, parts and labor
TSi's ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies. 

ILc Series System Architecture

                    ILc Series Low-Impedance Isolation Transformer Line Conditioner System Architecture Drawing

TSi Power also manufactures custom line conditioners.
For special applications, please call. 

Back to Top 

             

TSi Power Corporation ~ 1103 West Pierce Ave ~ Antigo, Wisconsin 54409 ~ Direct 715.623.0636 ~ 800.874.3160 (USA)
Fax 715.623.2426 ~ e-mail ~ sales@tsipower.com  ~  michaelg@carebase.com for comments/feedback on web site.
Privacy Statement    Copyright © 2001-2006 TSi Power Corporation

                                                        Hit Counter