* Best Viewed In Internet Explorer
| |
| TSi
Power’s ILc Series Line Conditioner provides the best all-round power
conditioning and surge protection for sensitive electronic equipment.
The integral isolation transformer provides 100% isolation from the
input ac line ~ the secondary neutral-to-ground bond eliminates all
surge voltages between neutral and ground. Surge protection and noise
filtering are superior to conventional surge protection and filtering
devices.
Typical ILc Line
Conditioner Applications
Designed for situations where reliability and
predictability matter to the enterprise.
Examples include: point-of-sale
terminals, telecommunications equipment, file servers, routers, digital
copiers, office machines, industrial controllers (PLC), automatic test
equipment (ATE), laboratory analyzers and other sensitive, specialized
microprocessor-based equipment.
Key ILc Power
Conditioning Benefits
ILc Series conditioners reduce the need for a
high quality ground and a dedicated line, while eliminating interference
from adjacent sources of disturbances. ILc contributes to enhanced
operation, improved repeatability, fewer reboots and system lock-ups and
extended operating life.
In addition, a reduction in equipment down time and service costs can be
expected.
How ILc Line Conditioners Work
The integral isolation transformer provides
complete isolation between the primary and secondary, and permits
bonding its output neutral to ground, which completely eliminates all
disturbances between neutral and ground, regardless of source. The
series inductance of the isolation transformer in combination with a
capacitive element and an MOV, provide superb noise filtering, as well
as coordinated multi-stage surge protection in accordance with the
principles of IEC 61312.3. |
| |
SPECIFICATIONS |
ILc-2400 |
ILc-3600 |
| |
Electrical |
|
Capacity in VA (Watts) |
2400 VA (2400 watts) |
3600
VA (3600 watts) |
| |
Transformer type |
Low-impedance
E-I Core isolation transformer |
| |
Input |
| |
Nominal voltage |
120
volts ac, single phase |
| |
Operating voltage |
100 - 130 volts ac |
| |
Nominal frequency |
60
Hz +/-3 |
| |
Circuit breaker rating |
5
amp |
10
amps |
| |
Ac input cord |
6
foot long ac power cord with NEMA 5-15P plug |
| |
Output |
| |
Nominal voltage |
120
volts ac, single phase |
| |
Power efficiency |
97%
(typical) |
| |
Total harmonic distortion |
<
1% |
| |
Surge protection |
A
three stage surge protection system consisting of
isolation transformer, capacitor and M.O.V. is included. |
| |
Surge test conditions |
Per
ANSI/IEEE C62.41-1991 test waveforms |
| |
Surge let-through voltages |
Single
pulse: L-N: 50V, L-G: 50V, N-G: 0.5V
Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V
Combination Wave: L-N: 250V, L-G: 250V, N-G: 0.5V
The measured rate of voltage
rise/fall (dV/dt of the remnant waveform
is less than 10V/mS
with input test waveform dV/dt of 6kV/mS. |
| |
Power on/off |
On/off rocker style power switch/circuit
breaker |
| |
Indicators |
Green LED indicates ac power is present |
| |
Ac receptacles
(Other options available) |
Four NEMA 5-20R and
four NEMA 5-15R |
Four NEMA 5-20R and
four NEMA 5-15R |
| |
Physical |
| |
Dimensions |
254mm (10")wide x 190mm (7.5")high x
368mm (14.5")deep |
| |
Weight |
27.3 kg (60 lbs) |
36.3 kg (80 lbs) |
| |
Safety |
| |
Agency approvals |
Designed to meet UL/cUL and IEC standards |
| |
Overcurrent protection |
User
resettable circuit breaker built-in |
| |
Environmental |
| |
Ambient temperature |
0
to +40°C,
90% Relative Humidity (non-condensing) |
| |
Warranty |
| |
Warranty |
5
year limited warranty, parts and labor |
|
TSi's ongoing product
improvement process makes specifications subject to change. Other
companies product names herein are for identification purposes only, and
may be trademarks of their respective companies. |
ILc Series System
Architecture

TSi Power also manufactures
custom line conditioners.
For special applications, please call.
Back to Top
|