Primary Contacts at TSi Power Corporation Quick Overview Of TSi's Highlights In Products & White Papers Link to the Google Primary Internet Search Page Search Page For The TSi Power Corporation Website Table of Contents for the TSi Power Corporation Website Link to the TSi Power Corporation Homepage

The TSi Power Corporation Home Page White Papers On Power Protection Strategies and Technologies Press Releases and News on TSi Power Corporation TSi Power & Surge Protection Products Overview Line Conditioners, Automatic Voltage Regulators, Low-Impedance and Ferroresonant Isolation Transformers Ac Automatic Voltage Regulators, Precision PWM, Tap-Switching and Ferroresonant Topologies Unipolar PWM Sine Wave Output Dc to Ac Inverters Automatic Transfer Switches For Enabling Redundant Power Sources e.g. 2 UPS Indoor Uninterruptible Power Systems Outdoor UPS With Extreme Wide Temperature Batteries for Harsh Environments Accessories for TSi Products, such as Rack-mounting Kits, Extra Battery Cabinets, etc. Pricing, RFQ's, RFP's and Getting Formal Quotations Frequently Asked Questions URL Links to some of TSi Power's Favorite Websites URL Link to the Free Adobe Acrobat PDF Reader Download Page

 * Best Viewed In Internet Explorer

 


ILc Series 
240VA, 120vac


Low-impedance isolation transformer
line conditioner

ILc-120-240 VA, 120VAC, Low-Impedance Isolation Transformer Line Conditioner With Neutral-Ground Bond Output

Click here for complete specifications in a
printer friendly Adobe Acrobat PDF format
TSi Power’s ILc Series line conditioner provides the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line ~ the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.

ILc Line Conditioner Applications
D
esigned for situations where reliability and predictability matter to the enterprise. 
Examples include: point-of-sale terminals, telecommunications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key ILc Power Conditioning Benefits
I
Lc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. 
In addition, a reduction in equipment down time and service costs can be expected.

How ILc Line Conditioners Work
T
he integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC 61312.3.


Key Features of the TSi Power Isolation Line Conditioner
Coordinated surge protection
per IEC 61312.3
Low-impedance 
isolation transformer
True isolation
Common-mode noise elimination
High efficiency

 

Advanced noise and interference
filter reduces dV/dt from
6kV/µS to less than 10V/µS
Four ac outlets
Quiet operation
Low weight
Five year warranty

 

   SPECIFICATIONS ILc-240
    Electrical
     Capacity in VA (Watts) 240 VA (240W)
     Transformer type Low-impedance E-I core isolation transformer
    Input
     Nominal voltage 120 volts ac, single phase
     Operating voltage 100 - 130 volts ac
     Nominal frequency 60 Hz +/-3
     Over-current protection User resettable circuit breaker built-in
     Circuit breaker rating 2 amps
     Ac input cord 6 foot long ac power cord with NEMA 5-15P plug
    Output
     Nominal voltage 120 volts ac, single phase
     Power efficiency 94% (typical)
     Total harmonic distortion < 1%
     Surge protection A three stage surge protection system consisting of 
isolation transformer, capacitor and M.O.V. is included
     Surge test conditions Per ANSI/IEEE C62.41-1991 test waveforms
     Surge let-through voltages Single pulse: L-N: 50V, L-G: 50V, N-G: 0.5V
Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V
Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V
The measured rate of voltage rise/fall (dV/dt of the remnant waveform 
is less than 10V/
mS with input test waveform dV/dt of 6kV/mS
     Ac receptacles Four (NEMA 5-15R)
    Physical
     Dimensions 152mm (6")wide x 102mm (4.0")high x 203mm (8.0")deep
     Weight 6.4 kg (14 lbs)
    Safety
     Agency approvals UL and cUL Listed
    Environmental
     Ambient temperature 0 to +40°C, 90% Relative Humidity (non-condensing)
    Warranty
     Warranty Five year limited warranty, parts and labor
TSi's ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies. 

ILc Series System Architecture  

                    ILc Series Low-Impedance Isolation Transformer Line Conditioner System Architecture Drawing

TSi Power also manufactures custom line conditioners.
For special applications, please call. 