* Best Viewed In Internet Explorer
| |
| TSi
Power’s ARm-1000 redundancy module ~ automatic bypass system is
recommended when no downtime from power outage is tolerated. Internet
service providers, critical servers and telecom equipment, and export
markets with bad power would find this technology valuable. The ARm
Series permits daisy chaining with any UPS, providing unlimited
redundancy using any combination of independant (separate) ac circuits,
UPS systems, generator-backed ac circuits, and so on.
Typical ARm
series applications
Designed
for situations where reliability and predictability matter to the
enterprise.
Examples: telecommunications equipment, export markets, file
servers, routers, digital copiers, office machines, industrial
controllers (PLC), automatic test equipment (ATE), laboratory analyzers
and other sensitive, specialized microprocessor-based equipment.
Key automatic
redundancy module benefits
The ARm
will provide uninterrupted ac to your load even in the event of UPS
failure. ARms your critical equipment against
extended power outages and catastrophic system shutdowns caused by
accidental circuit breaker trips, UPS overload conditions, weak or old
UPS batteries, routine & preventive maintenance of UPS, accidental
UPS shut down, loose power cords, or UPS failure. ARm-1000E
permits unlimited redundancy using any combination of independent
(separate) 230V ac circuits, UPS systems, generator-backed AC circuits, etc.
How ARm automatic
transfer switches work
The ARm
is fed by two AC power sources. When the primary power source detector
circuit senses a loss of power on that circuit, a relay immediately
switches the load over to the backup power source feed in less than 10
ms. This is fast enough to be invisible to computer switch-mode power
supplies. |
| |
SPECIFICATIONS |
ARm-1000 230V |
| |
Electrical |
|
Capacity in VA (Watts) |
2300
VA (2300 watts) |
| |
Switching technology |
Fast
operating / releasing relays |
| |
Input |
| |
Nominal voltage |
230
volts ac, single phase |
| |
Primary voltage |
190 ~ 260 volts ac |
| |
Backup voltage |
190
~ 260 volts ac |
| |
Frequency range |
50Hz
+/-5% |
| |
Over-current protection |
Both
primary and backup are protected by fuses |
| |
Fuse rating |
10
amps |
| |
Typical transfer time |
Less
than 10ms, primary to back-up and back-up to primary |
| |
Input/output wire size |
14
AWG Recommended |
| |
Ac inputs |
1.8m(6
ft.) three-conductor 14 AWG SJT cord w/ IEC 320 plugs |
| |
Output |
| |
Nominal voltage |
230
volts ac, single phase |
| |
Load regulation |
Better
than 2% from no load to full load |
| |
Power efficiency |
98%
or higher |
| |
Ac receptacles |
4
IEC 320 output receptacles |
| |
Indicators |
Green LED for primary ac presence, Yellow LED for backup ac
presence, Flashing Red LED for loss of primary or backup ac |
| |
Audible alarms |
Buzzer
beeps when Loss of Primary or Backup AC occurs. |
| |
Audible alarm switch |
Audible
alarm (buzzer) and alarm enable/disable switch |
| |
Alarms contacts interface |
A
rear-mounted DB-9 connector sends loss of primary ac
and loss of backup ac. (Pins 1 and 5 are used). |
| |
Physical |
| |
Dimensions |
254mmW
x 203mmD x 76mmH (10"wide x 8"deep x 3.2"high) |
| |
Weight |
2.7kg (6 lbs) |
| |
Rack mount option |
Front
mount kit: For a 19" rack: use # MK-5019A |
| |
Safety |
| |
In phase requirement |
Primary
and back-up ac must always be in phase |
| |
Environmental |
| |
Ambient temperature |
0°
to +40°C,
90% relative humidity (non-condensing) |
| |
Warranty |
| |
Warranty |
Two year limited warranty, parts and labor |
|
TSi's ongoing product
improvement process makes specifications subject to change. Other
companies product names herein are for identification purposes only, and
may be trademarks of their respective companies. |
ARm series
230V system
architecture

TSi Power also manufactures
custom (bespoke) automatic transfer switches.
For special applications, please call.
Back to top
|